Methodology & sources

Every formula, constant, and limitation of the sizing calculator, in the open. If you find an error, email support@whetstonetools.com.

1 · Heating load: a banded envelope-factor estimate

Design load = floor area × envelope factor × (70°F − design temp) × draftiness × duct factor

The envelope factor (Btu/h per sq ft per °F) comes in four tiers, each calibrated to published anchors — not retail folklore:

TierFactor rangeCalibration anchor
Tight (2015+ code / deep retrofit)0.10–0.14"Pretty Good House" ≈7.5 Btu/h·sqft at ΔT≈65–70°F (Energy Vanguard)
Code-built 1990s–2010s / older weatherized0.15–0.20≈12–14 Btu/h·sqft at ΔT=70°F for an IRC-2018-level home (GreenBuildingAdvisor)
Average older (1960–1990)0.21–0.28CEE Minnesota field data: median pre-1990 home ≈41,000 Btu/h at ΔT≈83°F, ~1,800–2,000 sqft → ≈0.25
Old & leaky (pre-1960)0.29–0.40upper practitioner band; verify with the fuel-bill method

Draftiness: ±10–15% (NEEP's infiltration guidance: weatherized ACHnat < 0.4, efficient new < 0.1). Ducts in unconditioned space: +20% (the +15–25% practitioner band). The result is always shown as a range — the spread is the honesty: a single number from a web form is false precision.

Applicability: heat loss scales with envelope surface, not floor area. Outside ~1,200–3,500 sq ft — or for 1.5-story, cathedral-ceiling, or heavily glazed homes — the tiers degrade; trust the fuel-bill cross-check and a professional Manual J instead.

2 · Cross-checks (measured beats estimated)

3 · Design temperature

The 99% heating design temperature for your county, embedded from the public-domain EPA ENERGY STAR County-Level Design Temperature Reference Guide (derived from ASHRAE 2013 Handbook of Fundamentals and ACCA Manual J 8th-ed conditions; lowest-station-in-county rule, which can run conservative in large mountainous counties — hence the manual override). Indoor design temperature: 70°F (NEEP). The 99% temp is exceeded ≈88 hours/year; the tool says so wherever it matters.

4 · Load line & capacity interpolation

Heating load line: linear from the design load at design temp to zero at 60°F (NEEP Sizing Support Tools User Guide; PNNL/ACEEE: "often estimated to be about 60°F"). Unit capacity: piecewise linear interpolation between the certified 47/17/5°F points (PNNL Building America formula). Below 5°F the tool extrapolates with a declining slope floored so a flattened (clamped) curve can't stay flat and overstate capacity, and floored again at zero — for verdicts only — and flags that some units shut off entirely below their minimum operating temperature, a field public data does not include.

Capacity-data quirk we correct for: the ENERGY STAR dataset mixes rated and maximum capacity semantics between temperature points (a unit can show 5°F capacity above its 47°F rating). Interpolating across mixed points overstates capacity exactly where cold-climate buyers live (5–17°F). The tool therefore monotonizes conservatively — each colder point is clamped to no more than the next warmer point — for all verdict math, displays the raw published values separately with a flag, and never presents 5°F/47°F as an official "capacity retention" metric.

5 · Verdict bands

TestBandSource
Sole-source passcapacity at design temp ≥ 100% of the high end of the load band and ≤120% of the band midpointNEEP 100–115% sole-source. Conservative asymmetry is ours: adequacy is judged against the high end. Oversize is judged against the midpoint, not the low end — with bands this wide (~1.33–1.40× low-to-high) a low-end oversize test makes "pass" mathematically unreachable.
Well-sized range90–120% of design loadNEEP Sizing Support Tools User Guide
With-backup target75–100% of the band midpointNEEP sizing guide 75–85% supplemental approach
Oversize warning>120% of the band midpointNEEP "avoid oversizing"; ACCA Manual S 3rd ed heating size factor limits

Backup heat, stated precisely: with a dual-fuel furnace, the furnace carries the entire load below the switchover temperature (heat pump and furnace generally can't run together on one air handler). Electric strips top up only the gap — and gap-sized strips will not keep the house warm if the compressor fails; emergency-heat sizing is a separate decision. Strip heat of 10–15 kW is a 200-amp-panel conversation: involve an electrician.

Defrost: certified points are steady-state. In humid 20–40°F weather, defrost cycles reduce delivered capacity, so computed balance points are optimistic — the tool shows this caveat whenever it applies, not just in coastal areas.

6 · What the tool refuses to do (and why)

Data sources

Disclaimer: estimates only — not engineering, installation, or purchasing advice. Heat pump performance varies with installation quality, refrigerant charge, ductwork, controls, and defrost behavior. Final selection requires a professional load calculation.